Setting Values - ABB REF610 Technical Reference Manual

Feeder protection relay
Hide thumbs Also See for REF610:
Table of Contents

Advertisement

1MRS755535
Table 5.1.4.10.-1

Setting values

Setting
Description
51P/I
(CT)
Pickup value of element 51P
n
51P TDLY
Operate time of element 51P
51P MODE
Time/current characteristic for
element 51P
51P TD IEC
Time multiplier 51P TD IEC
51P TD ANSI
Time multiplier 51P TD ANSI
51P RSET
Resetting time of element 51P
50P-1/I
(CT)
Pickup value of element 50P-1
n
50P-1 TDLY
Operate time of element 50P-1
50P-2/I
(CT)
Pickup value of element 50P-2
n
50P-2 TDLY
Operate time of element 50P-2
51N/I
(CT)
Pickup value of element 51N
n
51N TDLY
Operate time of element 51N
51N MODE
Time/current characteristic for
element 51N
51N TD IEC
Time multiplier 51N TD IEC
51N TD ANSI
Time multiplier 51N TD ANSI
51N RSET
Resetting time of element 51N
50N/I
(CT)
Pickup value of element 50N
n
50N TDLY
Operate time of element 50N
46 PICKUP
Pickup value of element 46 Pickup
46 TDLY
Operate time of element 46 Pickup
FLA
Full load current
τ
Time constant of element 49
49 Alarm
Alarm level of element 49
CBFAIL
Operate time of CBFAIL
79
Number of AR shots
Arc50P
Current limit Arc51P of element ARC 0.50...35.0 x I
ARC50N
Current limit Arc51N of element ARC 5.0...800% I
Feeder Protection Relay
Technical Reference Manual - ANSI Version
Switching between setting groups via a digital input has a higher
priority than via the HMI or with the parameter V150.
The setting values can be altered via the HMI or with a PC provided with Relay
Setting Tool.
Before the relay is connected to a system it must be assured that the relay has been
given the correct settings. If there is any doubt, the setting values should be read
with the relay trip circuits disconnected or tested with current injection; refer to
Section 8. Check lists for additional information.
Setting range
0.30...5.00 x I
0.05...300 s
0...9
0.05...1.00
1.0...15.0
0.05...2.50 s
0.50...35.0 x I
0.04...300 s
0.50...35.0 x I
0.04...30.0 s
1.0...100% I
0.05...300 s
0...9
0.05...1.00
1.0...15.0
0.05...2.50 s
5.0...800% I
0.05...300 s
10...100%
1...300 s
0.30...1.50 x I
1...200 min
50...100% 49 trip
0.10...60.0 s
0 = AR is not in use
1 = shot 1
2 = shot 1 and 2
3 = shot 1, 2 and 3
Default setting
(CT)
0.30 x I
n
0.05 s
0
0.05
1.0
0.05 s
(CT)
0.50 x I
n
0.04 s
(CT)
0.50 x I
n
0.04 s
(CT)
1.0% I
n
0.05 s
0
0.05
1.0
0.05 s
(CT)
5.0% I
n
0.05 s
100 %
60 s
(CT)
0.30 x I
n
1 min
95% 49 trip
0.10 s
0
(CT)
2.50 x I
n
(CT)
20.0% I
n
REF610
REF610
(CT)
n
(CT)
n
(CT)
n
(CT)
n
(CT)
n
(CT)
n
(CT)
n
(CT)
n
59