operating environment must meet the height, clearance, and environmental
requirements specified.
4.3.1
The UPS system installation requires a TN, TT or IT power distribution system
(the IT distribution system shall include a neutral wire).
The UPS system installation must meet the following guidelines:
The system must be installed on a level floor suitable for computer or
electronic equipment. The floor must be suitable for heavy weight and
wheeling.
The system must be installed in a temperature and humidity controlled
indoor area that is free of conductive contaminants.
The cabinet can be installed in line-up-and-match or standalone
configurations.
If you do not obey these guidelines your warranty may become void.
Do not stack anything on top of the UPS cabinet.
Do not stack the UPS 91PS/93PS C-model cabinet on top of any other similar
cabinet(s).
If installed on a shelf, use suitable supports to prevent the UPS from tipping
or dropping.
The UPS equipment operating environment must meet the weight requirements
shown in Table
Table 7: Dimensions
Shipping dimen-
sions (WxDxH)
Cabinet dimensions
(WxDxH)
Table 8: UPS cabinet weights with cardboard packaging
Shipping weight
Installed weight
Floor loading
©
Eaton Corporation plc 2018. All rights reserved.

Environmental and installation considerations

8
, and the size requirements shown in Table
C-model 8-20 kW
[mm]
540 x 857 x 705
335 x 750 x 645
C-model 8-20 kW
frame
98 kg
86 kg
310 kg/m
CAUTION
15/20 kW frame
[mm]
540 x 857 x 1460
335 x 750 x 1300
15/20 kW
frame
293 kg
280 kg
2
1,007 kg/m
Revision: 005
Document ID: P-164000493
User's and installation guide
7
.
30/40 kW frame
[mm]
750 x 820 x 1975
480 x 750 x 1750
30/40 kW
frame
558 kg
532 kg
2
1,478 kg/m
35 (117)