Example 2: More about the Function/Feature view control
The differences in the Input setpoints screens for Regular and Simplified mode are shown
below. Under Simplified mode, the Virtual Inputs and Remote Inputs are hidden for any
configuration change. However, the device will still accept and process virtual and remote
inputs based on what is configured during Regular mode. This way, Simplified
configuration mode does not change the behavior of the device.
Figure 4-5: Comparing the Inputs screens for Regular and Simplified mode
r
MA In
Rem In
Path:
Setpoints > Device > Config Mode
CONFIG MODE
Range: Simplified, Regular
Default: Regular
This setting allows selection of the configuration mode while the device is accessed by
the "Administrator" role. In Regular configuration mode, all values in settings/functions
can be edited. In Simplified configuration mode, selected settings/functions are hidden
or the values are read-only to enhance User eXperience (UX) with minimum setpoint
changes.
Simplified
..\Setpoints\Inputs
Item Name
Contact Inputs
Analog Inputs
Inputs
MA In
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 4: SETPOINTS