CHAPTER 4: SETPOINTS
ELEMENT
OPERANDS
Phase TOC
Ph TOC 1 PKP A
Ph TOC 1 PKP B
Ph TOC 1 PKP C
Ph TOC 1 PKP
Ph TOC 1 OP A
Ph TOC 1 OP B
Ph TOC 1 OP C
Ph TOC 1 OP
Ph TOC 2
Phase IOC
Ph IOC 1 PKP A
Ph IOC 1 PKP B
Ph IOC 1 PKP C
Ph IOC 1 PKP
Ph IOC 1 OP A
Ph IOC 1 OP B
Ph IOC 1 OP C
Ph IOC 1 OP
Ph IOC 2 OP
Phase Directional OC
Ph Dir OC REV A
Ph Dir OC REV B
Ph Dir OC REV C
Ph Dir OC REV
Phase UV
Ph UV 1 PKP
Ph UV 1 PKP A
Ph UV 1 PKP B
Ph UV 1 PKP C
Ph UV 1 OP
Ph UV 1 OP A
Ph UV 1 OP B
Ph UV 1 OP C
Ph UV 2
Phase OV
Ph OV 1 PKP
Ph OV 1 PKP A
Ph OV 1 PKP B
Ph OV 1 PKP C
Ph OV 1 OP
Ph OV 1 OP A
Ph OV 1 OP B
Ph OV 1 OP C
Ph OV 2
Pole Discordance
Pole Discord 1 OP
External PD 1 OP
Contact PD 1 OP
Current PD 1 OP
PD1 - A Fail to Open
PD1 - B Fail to Open
PD1 - C Fail to Open
PD1 - A Fail to Cls
PD1 - B Fail to Cls
PD1 - C Fail to Cls
Power Factor
PF 1 Switch-In
PF 1 Switch-Out
PF 1 Switch-In OP
PF 1 Switch-Out OP
PF 2
Pulse Output
Pos Wthrs Pulse OP
Neg Wthrs Pulse OP
Pos Varh Pulse OP
Neg Varh Pulse OP
Relay Service
In-Service
Remote Input
Rem Ip # ON
Rem Ip # OFF
Remote Modbus Device
FlexLogic Operand [X] On
FlexLogic Operand [X] Off
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
EVENT DESCRIPTION
Phase A of phase time overcurrent 1 has picked up
Phase B of phase time overcurrent 1 has picked up
Phase C of phase time overcurrent 1 has picked up
At least one phase of phase time overcurrent 1 has picked up
Phase A of phase time overcurrent 1 has operated
Phase B of phase time overcurrent 1 has operated
Phase C of phase time overcurrent 1 has operated
At least one phase of phase time overcurrent 1 has operated
The same set of operands as per Phase TOC 1
Phase A of phase IOC 1 has picked up
Phase B of phase IOC 1 has picked up
Phase C of phase IOC 1 has picked up
At least one phase of phase IOC overcurrent 1 has picked up
Phase A of phase IOC 1 has operated
Phase B of phase IOC 1 has operated
Phase C of phase IOC 1 has operated
At least one phase of phase IOC 1 has operated
The same set of operands as per Phase IOC 1
Phase A current in reverse direction
Phase B current in reverse direction
Phase C current in reverse direction
At least one phase current in reverse direction
At least one phase of phase undervoltage 1 has picked up
Phase A of phase undervoltage 1 has picked up
Phase B of phase undervoltage 1 has picked up
Phase C of phase undervoltage 1 has picked up
At least one phase of phase undervoltage 1 has operated
Phase A of phase undervoltage 1 has operated
Phase B of phase undervoltage 1 has operated
Phase C of phase undervoltage 1 has operated
The same set of operands as per Phase UV 1
At least one phase of phase overvoltage 1 has picked up
Phase A of phase overvoltage element 1 has picked up
Phase B of phase overvoltage element 1 has picked up
Phase C of phase overvoltage element 1 has picked up
At least one phase of phase overvoltage 1 has operated
Phase A of phase overvoltage element 1 has operated
Phase B of phase overvoltage element 1 has operated
Phase C of phase overvoltage element 1 has operated
The same set of operands as per Phase OV 1
Pole Discordance 1 operated
External pole discordance 1 detection operated
Contacts based detection of pole discordance 1 operated
Currents based detection of pole discordance 1 operated
Pole Discordance 1 Phase A failed to open
Pole Discordance 1 Phase B failed to open
Pole Discordance 1 Phase C failed to open
Pole Discordance 1 Phase A failed to close
Pole Discordance 1 Phase B failed to close
Pole Discordance 1 Phase C failed to close
The measured power factor has crossed the Switch-in setpoint
The measured power factor has crossed the Switch-Out setpoint
The PF1 Switch-In element operated
The PF1 Switch-Out element operated
The same set of operands as per PF 1
Positive Watthours pulse occurs at the end of the programed energy
increment
Negative Watthours pulse occurs at the end of the programed energy
increment
Positive VARhours pulse occurs at the end of the programed energy
increment
Negative VARhours pulse occurs at the end of the programed energy
increment
The relay is In-Service
# – any remote input number
[X] - the element number. Note the operand name will change depending
on what is programmed.
FLEXLOGIC
4–409