CHAPTER 4: SETPOINTS
NOTE:
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
1.
When the Counter is enabled and Digital Counter 1 Set to Pre-Set operand has value 1
(when the Counter is enabled and Digital Counter 1 Set to Pre-Set operand has value 0,
the Counter will be set to 0).
2.
When the Counter is running and Digital Counter 1 Set to Pre-Set operand changes
the state from 0 to 1 (Digital Counter 1 Set to Pre-Set changing from 1 to 0 while the
Counter is running has no effect on the count).
3.
When a reset or reset/freeze command is sent to the Counter and Digital Counter 1
Set to Pre-Set operand has the value 1 (when a reset or reset/freeze command is sent
to the Counter and Digital Counter 1 Set to Pre-Set operand has the value 0, the
Counter will be set to 0).
RESET
Range: Off, Any FlexLogic operand
Default: Off
The setpoint selects the FlexLogic operand for setting the count, either 0 or the pre-set
value depending on the state of the Counter 1 Set to Pre-set operand.
FREEZE/RESET
Range: Off, Any FlexLogic operand
Default: Off
The setpoint selects the FlexLogic operand for freezing (capturing) the accumulating
count value into a separate register with the associated date and time of the operation
while resetting the count to either 0 or the pre-set value depending on the state of the
"Counter 1 Set to Pre-set" operand.
FREEZE/COUNT
Range: Off, Any FlexLogic operand
Default: Off
The setpoint selects the FlexLogic operand for freezing (capturing) the accumulating
count value into a separate register with the associated date and time of the operation
while continuing counting. The present accumulated value and frozen (captured) value
with the associated date/time stamp are available as STATUS values. If control power is
interrupted, during the power-down operation, the accumulated and frozen (captured)
values are saved into non-volatile memory.
HI OUTPUT RELAY X
For details see
Common
EQL OUTPUT RELAY X
For details see
Common
LO OUTPUT RELAY X
For details see
Common
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
EVENTS
Range: Disabled, Enabled
Default: Enabled
The counter accumulated value can be reset to zero either by asserting an operand
programmed under Reset from the counter menu, executing the clear Digital Counters
command under the Records/Clear menu, or by setting the function of the counter to
"Disabled".
Setpoints.
Setpoints.
Setpoints.
MONITORING
4–287