FLEXLOGIC
4–420
INPUT 2 (-)
Range: Off, any FlexAnalog signal
Default: Off
This setting specifies the second input (inverted) to the FlexElement. Zero is assumed as
the input if this setting is set to "Off". For proper operation of the element at least one
input must be selected. Otherwise, the element will not assert its output operands.
This input should be used to invert the signal if needed for convenience, or to make the
element respond to a differential signal such as for a top-bottom oil temperature
differential alarm.
A warning message is displayed and the element does not operate if the two input
signals are of different types, for example if one tries to use active power and phase
angle to build the effective operating signal.
PICKUP
Range: -30.000 to 30.000 pu in steps of 0.001 pu
Default: 1.000
This setting specifies the operating threshold for the effective operating signal of the
element.
If the "Over" direction is set, the element picks up when the operating signal exceeds the
PICKUP value.
If the "Under" direction is set, the element picks up when the operating signal falls below
the PICKUP value.
The HYSTERESIS setting controls the element drop out.
Notice that both the operating signal and the pickup threshold can be negative when
facilitating applications such as reverse power alarms.
The FlexElement can be programmed to work with all analog values measured or
computed by the relay. The PICKUP setting is entered in pu values using the following
definitions of the base units:
Table 4-42: Definitions of the Base Unit for the FLEXELEMENT
Measured or calculated analog
value related to:
Voltage
Current
Power
Power Factor
Phase Angle
Harmonic Content
THD
Frequency
Volt/Hz
RTDs
2
I
t (arcing Amps)
Base Unit
V
= maximum nominal primary RMS value of the Input
BASE
1(+) and input 2(-) inputs
I
= maximum nominal primary RMS value of the Input 1(+)
BASE
and input 2(-) inputs
P
= maximum value of V
BASE
BASE
input 2(-) inputs
PF
= 1.00
BASE
DegBASE = 360 deg
H
= 100% of nominal
BASE
THD
= 100%
BASE
f
= nominal frequency as entered under the SYSTEM
BASE
SETUP menu
BASE = 1.00
BASE = 1.00°C
2
BASE = 2000 kA
*cycle
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL