CHAPTER 4: SETPOINTS
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
AUTORESET
Range: Disabled, Enabled
Default: Disabled
This setting enables the Tab Pushbutton Autoreset feature. The setting is applicable only
if the pushbutton is in "Latched" mode.
AUTORESET DELAY
Range: 0.2 to 600.0 s in steps of 0.1 s
Default: 1.0 s
This setting specifies the time delay for automatic Reset of the pushbutton when in the
"Latched" mode.
LOCK
Range: Any FlexLogic operand
Default: Off
This setting assigns a FlexLogic operand to inhibit pushbutton operation from the front
panel pushbuttons. This locking functionality is not applicable to pushbutton autoreset.
DROPOUT TIME
Range: 0.0 s to 600.0 s in steps of 0.1 s
Default: 0.0 s
This setting applies only to "Self-reset" mode and specifies the duration of the
pushbutton "active" status after the pushbutton has been released. The length of time
the operand remains on has no effect on the pulse duration.
The setting is required to set the duration of the pushbutton operating pulse.
EVENTS
Range: Disabled, Enabled
Default: Enabled
DEVICE
4–63