Configuration Setting - ABB RER670 Applications Manual

Relion 670 series, railway application
Hide thumbs Also See for RER670:
Table of Contents

Advertisement

1MRK 506 375-UEN A
12.4.5.3
Railway application RER670 2.2 IEC
Application manual
S1S2OPTR (A1A2)
BC12OPTR (sect.1)
QB12OPTR (bay 1/sect.2)
. . .
. . .
QB12OPTR (bay n/sect.2)
S1S2OPTR (A1A2)
BC12OPTR (sect.2)
QB12OPTR (bay 1/sect.1)
. . .
. . .
QB12OPTR (bay n /sect.1)
VPS1S2TR (A1A2)
VPBC12TR (sect.1)
VPQB12TR (bay 1/sect.2)
. . .
. . .
VPQB12TR (bay n/sect.1)
VPBC12TR (sect.2)
VPQB12TR (bay 1/sect.1)
. . .
. . .
VPQB12TR (bay n/sect.1)
EXDU_BS (A1A2)
EXDU_BC (sect.1)
EXDU_12(bay 1/sect.2)
. . .
. . .
EXDU_12 (bay n /sect.2)
EXDU_BC (sect.2)
EXDU_12 (bay 1/sect.1)
. . .
. . .
EXDU_12 (bay n /sect.1)
IEC04000491 V1 EN-US
Figure 99:
Signals from any bays for a bus-section circuit breaker between
sections B1 and B2

Configuration setting

If there is no other busbar via the busbar loops that are possible, then either the
interlocking for the QA1 open circuit breaker is not used or the state for BBTR is
set to open. That is, no busbar transfer is in progress in this bus-section:
BBTR_OP = 1
VP_BBTR = 1
>1
&
&
BBTR_OP
>1
&
&
VP_BBTR
&
EXDU_12
en04000491.vsd
Section 12
Control
M15111-57 v3
271