CBLifeAlmLevel: Alarm level for circuit breaker remaining life.
AccSelCal: Selection between the method of calculation of accumulated energy.
OperTimeDelay: Time delay between change of status of trip output and start of
main contact separation.

Event function EVENT

Identification
Function description
Event function
Application
When using a Substation Automation system with LON or SPA communication,
time-tagged events can be sent at change or cyclically from the IED to the station
level. These events are created from any available signal in the IED that is
connected to the Event function (EVENT). The EVENT function block is used for
LON and SPA communication.
Analog, integer and double indication values are also transferred through the
EVENT function.
Setting guidelines
The input parameters for the Event function (EVENT) can be set individually via
the local HMI (Main Menu/Settings / IED Settings / Monitoring / Event
Function) or via the Parameter Setting Tool (PST).
EventMask (Ch_1 - 16)
The inputs can be set individually as:
NoEvents
OnSet, at pick-up of the signal
OnReset, at drop-out of the signal
OnChange, at both pick-up and drop-out of the signal
AutoDetect, the EVENT function makes the reporting decision (reporting
criteria for integers have no semantic, prefer to be set by the user)
IEC 61850
IEC 60617
identification
identification
EVENT
S00946 V1 EN-US
Section 15
Monitoring
IP14590-1 v2
SEMOD167950-2 v2
ANSI/IEEE C37.2
device number
-
M12805-6 v11
IP14841-1 v1
M12811-3 v3
M12811-5 v3