ABB RER670 Applications Manual page 93

Relion 670 series, railway application
Hide thumbs Also See for RER670:
Table of Contents

Advertisement

1MRK 506 375-UEN A
Railway application RER670 2.2 IEC
Application manual
InvW2Curr=No
Then the internal calculations will be:
 
100
I
%
IDLW1 IDLW2
Diff
1
I
BaseW
 
I
%
Max IDLW
1 ,
IDLW
2
Bias
1
IECEQUATION203 V2 EN-US
The phase selection settings for the second instance of the T1PPDIF function shall
be:
PhSelW1=L2
PhSelW2=L1
InvW2Curr=Yes
Then the internal calculations will be:
 
100
I
%
IDLW1 IDLW2
Diff
2
I
BaseW
 
I
%
Max IDLW
1 ,
IDLW
2
Bias
2
IECEQUATION204 V2 EN-US
Transformer connection – example 3
132/66kV
I
U
U
132kV
I
v
V
IEC15000172 V2 EN-US
Figure 34:
Transformer connection – example 3
The HV currents I
and I
V
for the winding 1 side towards the T1PPDIF function. The LV currents I
shall be connected as IL1 and IL2 currents, respectively, for the winding 2 side
towards the T1PPDIF function.
100
I
I
V
S
I
1
BaseW
2
100
100
Max
I
,
I
V
S
I
I
BaseW
1
BaseW
2
100
I
I
U
S
I
1
BaseW
2
100
100
Max
I
,
I
U
S
I
I
BaseW
1
BaseW
2
shall be connected as IL1 and IL2 currents, respectively,
U
Section 6
Differential protection
GUID-945C3857-BE28-484D-B68F-7C9C3BB05441 v2
I
R
I
S
IEC15000172-2-en.vsdx
(Equation 10)
(Equation 11)
R
66kV
S
and I
S
R
87