ABB RER670 Applications Manual page 305

Relion 670 series, railway application
Hide thumbs Also See for RER670:
Table of Contents

Advertisement

1MRK 506 375-UEN A
Railway application RER670 2.2 IEC
Application manual
T1
I
T1
U
B
I L
Load
U
L
en06000486.vsd
IEC06000486 V1 EN-US
Figure 128:
Parallel transformers with equal rated data.
In the reverse reactance method, the line voltage drop compensation is used. The
original of the line voltage drop compensation function purpose is to control the
voltage at a load point further out in the network. The very same function can also
be used here to control the voltage at a load point inside the transformer, by
choosing a negative value of the parameter Xline.
Figure 129, shows a vector diagram where the principle of reverse reactance has
been introduced for the transformers in figure 128. The transformers are here
supposed to be on the same tap position, and the busbar voltage is supposed to give
a calculated compensated value U
I
=I
=(I
T1
T2
T1
IEC06000485 V3 EN-US
Figure 129:
Vector diagram for two transformers regulated exactly on target
voltage.
A comparison with figure
purpose of reverse reactance control is made with a value with opposite sign on X
T2
I
T2
that coincides with the target voltage USet.
L
R
I
=R
I
L
T1
L
T2
jX
I
=jX
L
T1
L
U
B
+I
)/2
T2
IEC06000485_2_en.vsd
126
gives that the line voltage drop compensation for the
Section 12
I
T2
Control
,
L
299

Advertisement

Table of Contents
loading

Table of Contents