Signals In Double-Breaker Arrangement - ABB RER670 Applications Manual

Relion 670 series, railway application
Hide thumbs Also See for RER670:
Table of Contents

Advertisement

1MRK 506 375-UEN A
12.4.7.3
Railway application RER670 2.2 IEC
Application manual
QB2OPTR(QB220OTR) (bay 1/sect.B2)
QB2OPTR(QB220OTR) (bay n/sect.B2)
DCOPTR (B1/B2)
VPQB2TR(VQB220TR) (bay 1/sect.B2)
VPQB2TR(VQB220TR) (bay n/sect.B2)
VPDCTR (B1/B2)
EXDU_BB (bay 1/sect.B2)
EXDU_BB (bay n/sect.B2)
EXDU_DC (B1/B2)
IEC04000509 V1 EN-US
Figure 117:
Signals from any bays in section B2 to a busbar earthing switch in
the same section
For a busbar earthing switch on bypass busbar C, these conditions are valid:
QB7OPTR (bay 1)
. . .
. . .
. . .
QB7OPTR (bay n)
VPQB7TR (bay 1)
. . .
. . .
. . .
VPQB7TR (bay n)
EXDU_BB (bay 1)
. . .
. . .
. . .
EXDU_BB (bay n)
IEC04000510 V1 EN-US
Figure 118:
Signals from bypass busbar to busbar earthing switch

Signals in double-breaker arrangement

The busbar earthing switch is only allowed to operate if all disconnectors of the bus
section are open.
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
&
&
&
Section 12
Control
BB_DC_OP
&
VP_BB_DC
&
EXDU_BB
&
en04000509.vsd
BB_DC_OP
VP_BB_DC
EXDU_BB
en04000510.vsd
M15053-83 v4
283