Setting Guidelines - ABB RER670 Applications Manual

Relion 670 series, railway application
Hide thumbs Also See for RER670:
Table of Contents

Advertisement

Section 12
Control
12.7.3
12.8
12.8.1
12.8.2
334
VSGAPC
PSTO
INTONE
IPOS1
IPOS2
NAM_POS1
OFF
NAM_POS2
ON
IEC07000112 V3 EN-US
Figure 139:
Control of Autorecloser from local HMI through Selector mini switch
VSGAPC is also provided with IEC 61850 communication so it can be controlled
from SA system as well.

Setting guidelines

Selector mini switch (VSGAPC) function can generate pulsed or steady commands
(by setting the Mode parameter). When pulsed commands are generated, the length
of the pulse can be set using the tPulse parameter. Also, being accessible on the
single line diagram (SLD), this function block has two control modes (settable
through CtlModel): Dir Norm and SBO Enh.
Generic communication function for Double Point
indication DPGAPC
Identification
Function description
Generic communication function for
Double Point indication
Application
Generic communication function for Double Point indication (DPGAPC) function
block is used to send double point position indication to other systems, equipment
or functions in the substation through IEC 61850-8-1 or other communication
protocols. It is especially intended to be used in the interlocking station-wide
logics. To be able to get the signals into other systems, equipment or functions, one
must use other tools, described in the Engineering manual, and define which
CMDPOS12
ON
CMDPOS21
OFF
IEC 61850
identification
DPGAPC
1MRK 506 375-UEN A
INVERTER
OUT
INPUT
SMBRREC
SETON
IEC07000112-3-en.vsd
GUID-E16EA78F-6DF9-4B37-A92D-5C09827E2297 v3
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
Railway application RER670 2.2 IEC
Application manual
SEMOD158807-4 v4
SEMOD55384-1 v4
SEMOD55391-5 v8