Section 8
Current protection
8.9.3
194
resistance R
should not exceed a certain value regardless of atmospheric
G,I
conditions.
Setting guidelines
The parameters for transformer tank protection TPPIOC are set via the local HMI
or PCM600.
The setting parameters for the transformer tank protection TPPIOC are described
below:
Common base IED values for primary current (setting IBase) is set in a Global base
values for settings function GBASVAL setting.
GlobalBaseSel: Selects the global base value group used by the function to define
(IBase).
I>: Instantaneous peak current start value in % of IBase.
1MRK 506 375-UEN A
GUID-916B2550-5C16-47F7-9782-7DD6FABAA0A2 v1
Railway application RER670 2.2 IEC
Application manual