ABB RER670 Applications Manual page 323

Relion 670 series, railway application
Hide thumbs Also See for RER670:
Table of Contents

Advertisement

1MRK 506 375-UEN A
Railway application RER670 2.2 IEC
Application manual
Over-Current
Total block via settings
Total block via configuration
Analog input error
Automatic block via settings
Automatic block via configuration
Under-Voltage
Command error
Position indication error
Tap changer error
Reversed Action
Circulating current
Communication error
Master-follower method
When the master is blocked, the followers will not tap by themselves and there is
consequently no need for further mutual blocking. On the other hand, when a
follower is blocked there is a need to send a mutual blocking signal to the master.
This will prevent a situation where the rest of the group otherwise would be able to
tap away from the blocked individual, and that way cause high circulating currents.
Thus, when a follower is blocked, it broadcasts a mutual block on the horizontal
communication. The master picks up this message, and blocks its automatic
operation as well.
Besides the conditions listed above for mutual blocking with the circulating current
method, the following blocking conditions in any of the followers will also cause
mutual blocking:
Master-follower out of position
Master-follower error (No master/More than one master)
General
It should be noted that partial blocking will not cause mutual blocking.
TR8ATCC, which is the "source" of the mutual blocking will set its AUTOBLK
output as well as the output which corresponds to the actual blocking condition for
example, IBLK for over-current blocking. The other TR8ATCCs that receive a
mutual block signal will only set its AUTOBLK output.
The mutual blocking remains until TR8ATCC that dispatched the mutual block
signal is de-blocked. Another way to release the mutual blocking is to force
TR8ATCC, which caused mutual blocking to Single mode operation. This is done
by activating the binary input SNGLMODE on TR8ATCC function block or by
setting the parameter OperationPAR to Off from the built-in local HMI or PST.
TR8ATCC function can be forced to single mode at any time. It will then behave
exactly the same way as described in section
Section 12
"Automatic voltage control for a
Control
317