When the setting Operation is set to Off, the behavior is set to Off and it is not
possible to override it. When a behavior of a function is Offthe function will not
execute.
When IEC 61850 Mod of a function is set to Off or Blocked, the
Start LED on the LHMI will be set to flashing to indicate the
abnormal operation of the IED.
The IEC 61850-7-4 gives a detailed overview over all aspects of the test mode and
other states of mode and behavior.
When the Beh of a component is set to Test, the component is not blocked and
all control commands with a test bit are accepted.
When the Beh of a component is set to Test/blocked, all control commands
with a test bit are accepted. Outputs to the process via a non-IEC 61850 link
data are blocked by the LN. Only process-related outputs on LNs related to
primary equipment are blocked. If there is an XCBR, the outputs EXC_Open
and EXC_Close are blocked.
When the Beh of a component is set to Blocked, all control commands with a
test bit are accepted. Outputs to the process via a non-IEC 61850 link data are
blocked by the LN. In addition, the components can be blocked when their Beh
is blocked. This can be done if the component has a block input. The block
status of a component is shown as the Blk output under the Test/Function
status menu. If the Blk output is not shown, the component cannot be blocked.

Setting guidelines

There are two possible ways to place the IED in the TestMode= On" state. If, the
IED is set to normal operation (TestMode = Off), but the functions are still shown
being in the test mode, the input signal INPUT on the TESTMODE function block
might be activated in the configuration.
Forcing of binary input and output signals is only possible when the IED is in IED
test mode.
Time synchronization TIMESYNCHGEN
Setting guidelines
All the parameters related to time are divided into two categories: System time and
Synchronization.
Section 21
Basic IED functions
M15260-3 v6
IP1750-1 v2