ABB RER670 Applications Manual page 157

Relion 670 series, railway application
Hide thumbs Also See for RER670:
Table of Contents

Advertisement

1MRK 506 375-UEN A
Railway application RER670 2.2 IEC
Application manual
Trafo 132/15kV
U
132kV
V
IEC15000302 V2 EN-US
Trafo 132/66kV
U
132kV
V
IEC15000304 V2 EN-US
Figure 44:
Railway transformers connection examples
ZGTPDIS function can be used as primary protection as well as backup protection
for the transformer. It protects both HV and LV side of the transformer. The
protection is designed to operate for earth faults and phase faults in the transformer
and the associated lines.
Zone 1 can be used to provide high-speed protection for faults in the HV winding
of the transformer. Zone 2 can be used to cover the entire transformer and
substation LV busbar. Zone 3 can be used to cover power system faults beyond the
LV busbar.
Backup impedance protection characteristics
The characteristics of zone 1, zone 2 and zone 3 are shown in Figure 45. All zones
have either offset mho or non-directional quadrilateral characteristics with
adjustable reach in forward and reverse direction. Quadrilateral characteristics have
2-phase to 1-phase interconnection
2-phase to 2-phase interconnection
Section 7
Impedance protection
15kV
IEC15000302-1-en.vsdx
66kV
IEC15000304-2-en.vsdx
V
U
V
151