ABB RER670 Applications Manual page 183

Relion 670 series, railway application
Hide thumbs Also See for RER670:
Table of Contents

Advertisement

1MRK 506 375-UEN A
Railway application RER670 2.2 IEC
Application manual
Where
I
is the capacitive earth fault current at a non-resistive phase-to-earth fault
j
X
is the capacitive reactance to earth
c
In a system with a neutral point resistor (resistance earthed system) the impedance
Z
can be calculated as:
0
j X
2
R
c
n
Z
0
j X
2
R
c
n
IECEQUATION16032 V1 EN-US
Where
R
is the resistance of the neutral point resistor
n
In many systems there is also a neutral point reactor (Petersen coil) connected to
one or more transformer neutral points. In such a system the impedance Z
calculated as:
 
Z
jX
/ /2
R
/ / 2
j X
0
c
n
IECEQUATION16033 V1 EN-US
Where
X
is the reactance of the Petersen coil. If the Petersen coil is well tuned we have 2X
n
this case the impedance Z
Now consider a system with an earthing via a resistor giving higher earth fault
current than the high impedance earthing. The series impedances in the system can
no longer be neglected. The system with a single phase to earth fault can be
described as in Figure 58.
4
R X X
n
n
c
n
2
X X
j R
2
2
n
c
n
will be: Z
= 2R
0
0
n
Section 8
Current protection
(Equation 45)
0
X
X
n
c
(Equation 46)
n
can be
= X
In
c
177

Advertisement

Table of Contents
loading

Table of Contents