Setting Example - ABB RER670 Applications Manual

Relion 670 series, railway application
Hide thumbs Also See for RER670:
Table of Contents

Advertisement

1MRK 506 375-UEN A
14.14.4
Railway application RER670 2.2 IEC
Application manual
EqualBandHigh: This setting is used to set the equal condition high band limit in %
of reference value. This high band limit will act as reset limit for INHIGH output
when INHIGH.
EqualBandLow: This setting is used to set the equal condition low band limit in %
of reference value. This low band limit will act as reset limit for INLOW output
when INLOW.

Setting example

Let us consider a comparison is to be done between current magnitudes in the
range of 90 to 110 with nominal rating is 100 and the order is kA.
For the above condition the comparator can be designed with settings as follows,
EnaAbs = Absolute
RefSource = Set Value
SetValue = 100
RefPrefix = Kilo
EqualBandHigh = 5.0 % of reference value
EqualBandLow = 5.0 % of reference value
Operation
The function will set the outputs for the following conditions,
INEQUAL will set when the INPUT is between the ranges of 95 to 105 kA.
INHIGH will set when the INPUT crosses above 105 kA.
INLOW will set when the INPUT crosses below 95 kA.
If the comparison should be done between two current magnitudes then those
current signals need to be connected to function inputs, INPUT and REF. Then the
settings should be adjusted as below,
EnaAbs = Absolute
RefSource = Input REF
EqualBandHigh = 5.0 % of reference value
EqualBandLow = 5.0 % of reference value.
Section 14
Logic
GUID-E7070CF6-B44B-4799-BE18-5C75B9FE2A87 v2
377

Advertisement

Table of Contents
loading

Table of Contents