Operating Guide ECL Comfort 310, application A377
MENU > Settings > Application
Circ. P priority
Choose whether the DHW circulation pump should be ON during DHW
heating.
See Appendix "Parameter ID overview"
OFF:
The DHW circulation pump is switched OFF during DHW
heating.
ON:
The DHW circulation pump is not switched OFF during
DHW heating.
MENU > Settings > Application
Supply T mon.
Selection of functions related to temperature sensor S10.
See Appendix "Parameter ID overview"
OFF:
S10 acts as return temperature sensor.
Limitation value and Influence factors are set as
described in the section 'Return limit' .
ON:
S10 acts as supply temperature sensor and return
temperature sensor.
A:
The supply temperature is monitored and enables the
DHW charging.
B:
Return temperature limit function: Limitation value
and influence factors are set as described in the section
'Return limit' .
The return temperature limitation is activated 4 minutes
after start of DHW charging.
MENU > Settings > Application
P charge delay (Charging pump, delayed start)
Conditions for switching the DHW heating / charging pump ON at DHW
heating / charging demand.
Correct setting can avoid discharging.
See Appendix "Parameter ID overview"
OFF:
DHW heating / charging pump is switched ON when
DHW heating / charging temperature is OK.
0:
DHW heating / charging pump is switched ON.
Value: DHW heating / charging pump is switched ON after the
set number of minutes.
VI.GU.F6.02
1x055
When the 'Circ. P priority' is set to OFF, the schedule for the DHW
circulation pump is overruled.
1x056
If ON is selected, the temperature sensor S10 can be placed in the
supply line.
The DHW charging pump P4 will start when the supply temperature
(S10) becomes higher than the DHW tank temperature (S6).
If no influence from return temperature limit is desired, the influence
factors set in ID nos. 13035 / 13036 must be set to 0.0.
1x059
When the setting "OFF" is selected, the temperature sensor for DHW
heating / charging must be placed in the heat-exchanger.
© Danfoss | 2017.10 | 97