Danfoss ECL Comfort 310 Operating Manual page 16

Application a377
Hide thumbs Also See for ECL Comfort 310:
Table of Contents

Advertisement

Operating Guide ECL Comfort 310, application A377
Advice for settings:
A377.2, ex. b
A377.2, ex. c
Circuit 1 must be able to receive the heat demand from circuit 2
and the DHW-heating demand from circuit 3.
Issue:
Heating circuit (1):
Heat demand
* This value is added to the heating demand value circuit 2 and 3.
Circuit 2 must be able to send the heat demand to circuit 1.
Issue:
Heating circuit (2):
Heat demand
Circuit 3 must be able to send the DHW-heating demand to
circuit 1.
Issue:
DHW circuit (3):
Heat demand
DHW circulation pipe can be connected to the DHW tank at 'A'
for internal circulation or to the heat-exchanger at 'B' for external
circulation.
Issue:
DHW circuit (3):
Internal DHW circulation
DHW circuit (3):
External DHW circulation
16 | © Danfoss | 2017.10
Navigation:
MENU \ Settings \ Application: 'Demand offset'
Navigation:
MENU \ Settings \ Application: 'Send desired T'
Navigation:
MENU \ Settings \ Application: 'Send desired T'
Navigation:
MENU \ Settings \ Application: 'Cont. T control'
MENU \ Settings \ Application: 'Cont. T control'
ID no.:
Recommended
setting:
11017
3 K*
ID no.:
Recommended
setting:
12500
ON
ID no.:
Recommended
setting:
13500
ON
ID no.:
Recommended
setting:
13054
OFF
13054
ON
VI.GU.F6.02