Operating Guide ECL Comfort 310, application A377
MENU > Settings > Flow / power limit
Limit (limitation value)
This value is in some applications a calculated limitation value, based on the
actual outdoor temperature.
In other applications the value is a selectable limitation value.
See Appendix "Parameter ID overview"
MENU > Settings > Flow / power limit
Adapt. time (adaptation time)
Controls how fast the flow / power limitation adapts to the desired
limitation.
See Appendix "Parameter ID overview"
OFF:
The control function is not influenced by the 'Adapt.
time' .
Minor
The desired temperature is adapted quickly.
value:
Major
The desired temperature is adapted slowly.
value:
MENU > Settings > Flow / power limit
Filter constant
The value of the filter constant determines the dampening of the measured
value.
The higher the value, the more dampening.
By this, a too quick change of the measured value can be avoided.
See Appendix "Parameter ID overview"
Minor
Lower dampening
value:
Major
Higher dampening
value:
MENU > Settings > Flow / power limit
Units
Choice of units for measured values.
See Appendix "Parameter ID overview"
Flow values are expressed as l/h or m³/h
Power values are expressed as kW, MW or GW.
80 | © Danfoss | 2017.10
1x111
1x112
If the 'Adapt. time' is too low, there is a risk of unstable control.
1x113
1x115
List for setting range of 'Units':
l/h
m³/h
kW
MW
GW
VI.GU.F6.02