Operating Guide ECL Comfort 310, application A377
MENU > Settings > Application
M exercise (valve exercise)
Exercises the valve to avoid blocking in periods without heat demand.
See Appendix "Parameter ID overview"
OFF:
The valve exercise is not active.
ON:
The valve opens for 7 minutes and closes for 7 minutes
every third day at noon (12:00 hours).
MENU > Settings > Application
P post-run
Heating applications:
The circulation pump in the heating circuit can be ON for a number of
minutes (m) after heating stop. Heating stop is when the desired flow
temperature gets lower than the setting in 'P heat T' (ID no. 1x078).
Cooling applications:
The circulation pump in the cooling circuit can be ON for a number of
minutes (m) after cooling stop. Cooling stop is when the desired flow
temperature gets higher than the setting in 'P cool T' (ID no. 1x070).
This P post-run function can utilize the remaining energy in for example a
heat exchanger.
See Appendix "Parameter ID overview"
0:
The circulation pump stops immediately after heating
or cooling stop.
Value: The circulation pump is ON for the set time after heating
or cooling stop.
MENU > Settings > Application
Char. P post-run (DHW charging pump, post-run)
Set the DHW charging pump post-run time (minutes). The DHW charging
pump can continue to be switched ON after the DHW heating procedure in
order to utilize the remaining heat in the heat exchanger.
See Appendix "Parameter ID overview"
Value: Set the number of minutes for the post-run.
VI.GU.F6.02
1x023
1x040
1x042