Operating Guide ECL Comfort 310, application A377
MENU > Settings > Return limit
Infl. - min. (return temp. limitation - min. influence)
Determines how much the desired flow temperature will be influenced if the
return temperature is lower than the calculated limit.
See Appendix "Parameter ID overview"
Influence higher than 0:
The desired flow temperature is increased, when the return
temperature gets below the calculated limit.
Influence lower than 0:
The desired flow temperature is decreased, when the return
temperature gets below the calculated limit.
MENU > Settings > Return limit
Adapt. time (adaptation time)
Controls how fast the return temperature adapts to the desired return
temperature limit (Integration control).
See Appendix "Parameter ID overview"
OFF:
The control function is not influenced by the 'Adapt.
time' .
Minor
The desired temperature is adapted quickly.
value:
Major
The desired temperature is adapted slowly.
value:
MENU > Settings > Return limit
Priority (priority for return temp. limitation)
Choose whether the return temperature limitation should overrule the set
min. flow temperature 'Temp. min.' .
See Appendix "Parameter ID overview"
OFF:
The min. flow temperature limit is not overruled.
ON:
The min. flow temperature limit is overruled.
VI.GU.F6.02
Example
The return limit is active below 50 °C.
1x036
The influence is set to -3.0.
The actual return temperature is 2 degrees too low.
Result:
The desired flow temperature is changed by -3.0 x 2 = -6.0 degrees.
Normally, this setting is 0 in district heating systems because a lower
return temperature is acceptable.
Typically, this setting is higher than 0 in boiler systems to avoid a too
low return temperature (see also 'Infl. - max.').
1x037
The adaptation function can correct the desired flow temperature
with max. 8 K.
1x085
If you have a DHW application:
Please also see 'Parallel operation' (ID 11043).
If you have a DHW application:
When dependent parallel operation is in function:
Desired flow temperature for the heating circuit will be minimum
limited, when "Priority for return temperature" (ID 1x085) is set
to OFF.
Desired flow temperature for the heating circuit will not be
minimum limited, when "Priority for return temperature"
(ID 1x085) is set to ON.
© Danfoss | 2017.10 | 77