Operating Guide ECL Comfort 310, application A377
Advice for settings:
A377.2, ex. a
Circuit 1 must be able to receive the DHW-heating demand from
circuit 3.
Issue:
Heating circuit (1):
Heat demand
* This value is added to the DHW-heating demand from circuit 3.
Circuit 3 must be able to send the DHW-heating demand to
circuit 1.
Issue:
DHW circuit (3):
Heat demand
DHW circulation pipe can be connected to the DHW tank at 'A'
for internal circulation or to the heat-exchanger at 'B' for external
circulation.
Issue:
DHW circuit (3):
Internal DHW circulation
DHW circuit (3):
External DHW circulation
VI.GU.F6.02
Navigation:
MENU \ Settings \ Application: 'Demand offset'
Navigation:
MENU \ Settings \ Application: 'Send desired T'
Navigation:
MENU \ Settings \ Application: 'Cont. T control'
MENU \ Settings \ Application: 'Cont. T control'
ID no.:
Recommended
setting:
11017
3 K*
ID no.:
Recommended
setting:
13500
ON
ID no.:
Recommended
setting:
13054
OFF
13054
ON