2.5.4 Electrical connections, Pt 1000 temperature sensors and signals
See the Installation Guide (delivered with the application key) for
sensor and input connections.
A377:
Sen-
Description
sor
S1
Outdoor temperature sensor*
S2
Return temperature sensor
S3
Flow temperature sensor**
S4
Flow temperature sensor**
S5
Return temperature sensor
S6
DHW tank temperature sensor,
upper***
S7
Voltage signal (0-10 V) for
external control of desired flow
temperature, heating circuit 1
S8
A377.1, A377.2:
DHW tank temperature sensor,
lower
A377.3:
DHW circulation return
S9
A377.1, A377.3
DHW heating / charging
temperature sensor**
A377.2
DHW heating temperature sensor**
(S9)
A377.1, A377.3:
Alternative position for DHW
heating / charging temperature
sensor**
S10
A377.1, A377.3:
DHW return temperature
sensor****
Alternative: Supply temperature
sensor
A377.2:
DHW charging temperature
sensor****
*
If the outdoor temperature sensor is not connected or the
cable is short-circuited, the controller assumes that the
outdoor temperature is 0 (zero) °C.
**
The sensor must always be connected in order to have the
desired functionality. If the sensor is not connected or the
cable is short-circuited, the motorized control valve closes
(safety function).
*** This sensor is used if only one tank temperature sensor is
required.
**** The sensor must always be connected in order to have the
desired functionality.
VI.GU.F6.02
Type
(recomm.)
ESMT
ESM-11 / ESMB /
ESMC / ESMU
ESM-11 / ESMB /
ESMC / ESMU
ESM-11 / ESMB /
ESMC / ESMU
ESM-11 / ESMB /
ESMC / ESMU
ESMB /
ESMU
ESMB /
ESMU
ESM-11 / ESMB /
ESMC / ESMU
ESM-11 / ESMB /
ESMC / ESMU
ESM-11 / ESMB /
ESMC / ESMU
ESM-11 / ESMB /
ESMC / ESMU
© Danfoss | 2017.10 | 27