Operating Guide ECL Comfort 310, application A377
DHW circuit
A flow or energy meter can be connected (M-bus signal) to the ECL
controller in order to limit the flow or consumed power.
When the flow / power gets higher than the set limit, the controller
gradually reduces the desired flow temperature to obtain an
acceptable max. flow or power consumption.
Parameters indicated with an ID no. like "1x607" mean a universal
parameter.
x stands for circuit / parameter group.
MENU > Settings > Flow / power limit
Input type
Choice of M-bus signal from energy meter number 1 ... 5. Only possible
in ECL Comfort 310.
See Appendix "Parameter ID overview"
OFF:
No M-bus signal acquired.
EM1 ... EM5: Energy meter number.
MENU > Settings > Flow / power limit
Actual (actual flow or power)
The value is the actual flow or power based on the signal from flow / energy
meter.
VI.GU.F6.02
=
X
Time
=
Y
Flow or power
# 1 # =
Flow or power limit
# 2 # =
Actual flow or energy
# 3 # =
Desired flow temperature
1x109
Flow or power limitation is based on M-bus signal (ECL Comfort 310
controllers only).