Operating Guide ECL Comfort 310, application A377
MENU > Settings > Flow temperature
Desired T (Desired flow temperature)
When the ECL Comfort is in override mode, type "Const. T", the desired flow
temperature can be set.
A "Const. T" related return temperature limitation can also be set. See MENU
> Settings > Return limit > 'Con. T, ret. T lim. '
See Appendix "Parameter ID overview"
MENU > Settings > Flow temperature
Temp. min.
See Appendix "Parameter ID overview"
Set the min. flow temperature for the system. The desired flow
temperature will not be lower than this setting. Adjust the factory
setting, if required.
MENU > Settings > Flow temperature
Temp. max.
See Appendix "Parameter ID overview"
Set the max. flow temperature for the system. The desired
temperature will not be higher than this setting. Adjust the factory
setting, if required.
VI.GU.F6.02
1x004
Override mode
When ECL Comfort is in Scheduled mode, a contact (switch) signal can
be applied to an input in order to override to Comfort, Saving, Frost
Protection or Constant temperature. As long as the contact (switch)
signal is applied, the override is active.
The "Desired T" value can be influenced by:
temp. max.
temp. min.
room temp. limit
return temp. limit
flow / power limit
1x177
'Temp. min. ' is overruled if 'Total stop' is active in Saving mode or
'Cut-out' is active.
'Temp. min. ' can be overruled by the influence from the return
temperature limitation (see 'Priority').
The setting for 'Temp. max. ' has higher priority than 'Temp. min. ' .
1x178
The setting of 'heat curve' is possible for heating circuits only.
The setting for 'Temp. max. ' has higher priority than 'Temp. min. ' .