Operating Guide ECL Comfort 310, application A377
Example, minimum return temperature limitation;
return temperature gets lower than limit
Parameters indicated with an ID no. like "1x607" mean a universal
parameter.
x stands for circuit / parameter group.
VI.GU.F6.02
= Temperature
T
= Temperature
Y
= Time
X
# 1 # = Return temperature
# 2 # = Return temperature limit
# 3 # = Desired flow temperature
# 4 # = Action point
The return temperature limitation for the DHW circuit is based on the
setting in 'Limit (return temp. limitation)' .
The influence factors are set in the heating circuit.
If the return temperature limitation value in the heating circuit is
higher than the return temperature limitation value in the DHW circuit,
the highest value is used.
© Danfoss | 2017.10 | 73