Danfoss ECL Comfort 310 Operating Manual page 114

Application a377
Hide thumbs Also See for ECL Comfort 310:
Table of Contents

Advertisement

Operating Guide ECL Comfort 310, application A377
MENU > Settings > Alarm
Delay, example
If an alarm condition from either 'Upper difference' or 'Lower difference' is
present for a longer time than the set delay (in minutes), the alarm function
is activated.
See Appendix "Parameter ID overview"
Value:
The alarm function will be activated if the alarm
condition remains after the set delay.
MENU > Settings > Alarm
Lowest temp.
The alarm function will not be activated if the desired flow / duct
temperature is lower than the set value.
See Appendix "Parameter ID overview"
114 | © Danfoss | 2017.10
Delay, example
1x149
=
X
Time
=
Y
Temperature
=
# 1 #
Lower difference
=
# 2 #
Desired flow temperature
=
# 3 #
Actual flow temperature
=
# 4 #
Delay (ID 1x149)
1x150
If the cause of the alarm disappears, the alarm indication and output
also disappear.
VI.GU.F6.02