Operating Guide ECL Comfort 310, application A377
MENU > Settings > Alarm
Upper difference
The alarm is activated if the actual flow / duct temperature increases more
than the set difference (acceptable temperature difference above the desired
flow / duct temperature). See also 'Delay' .
See Appendix "Parameter ID overview"
OFF:
The related alarm function is not active.
Value:
The alarm function is active if the actual temperature
gets above the acceptable difference.
MENU > Settings > Alarm
Lower difference
The alarm is activated if the actual flow / duct temperature decreases more
than the set difference (acceptable temperature difference below the desired
flow / duct temperature). See also 'Delay' .
See Appendix "Parameter ID overview"
OFF:
The related alarm function is not active.
Value:
The alarm function is active if the actual temperature
gets below the acceptable difference.
VI.GU.F6.02
Upper difference
1x147
=
X
Time
=
Y
Temperature
=
# 1 #
Upper difference
=
# 2 #
Desired flow temperature
Lower difference
1x148
=
X
Time
=
Y
Temperature
=
# 1 #
Lower difference
=
# 2 #
Desired flow temperature