Danfoss ECL Comfort 310 Operating Manual page 94

Application a377
Hide thumbs Also See for ECL Comfort 310:
Table of Contents

Advertisement

Operating Guide ECL Comfort 310, application A377
MENU > Settings > Application
Demand offset
The desired flow temperature in heating circuit 1 can be influenced by the
demand for a desired flow temperature from another controller (slave) or
another circuit.
See Appendix "Parameter ID overview"
OFF:
The desired flow temperature in circuit 1 is not
influenced by the demand of any other controller (slave
or circuit 2).
Value: The desired flow temperature is increased by the set
value in 'Demand offset' , if the demand of the slave /
circuit 2 is higher.
MENU > Settings > Application
P exercise (pump exercise)
Exercises the pump to avoid blocking in periods without heat demand.
See Appendix "Parameter ID overview"
OFF:
The pump exercise is not active.
ON:
The pump is switched ON for 1 minute every third day at
noon (12:14 hours).
94 | © Danfoss | 2017.10
Heating application
1x017
=
X
Time
=
Y
Desired flow temperatures
=
# 1 #
Demand offset
=
# 2 #
Desired flow temperature, master
=
# 3 #
Desired flow temperature, slave
'Demand offset' with a value is to be used in the Master controller only.
The function of 'Demand offset' can compensate for heat losses
between master and slave controlled systems.
When setting "Demand offset" to a value, the return temperature
limitation will react according to the highest limitation value (Heating
/ DHW).
1x022
VI.GU.F6.02