A368 and A376 and contains only a description of the extended heat cut-out functionality. The extended heat cut-out functionality can be realized with ECL Comfort 210 and ECL Comfort 310. For information on general functions please consult the installation guide for the application key in question.
Page 3
(e.g. 12174 - A266.9). Disposal Note This product should be dismantled and its components sorted, if possible, in various groups before recycling or disposal. Always follow the local disposal regulations. Danfoss District Energy VI.GU.U1.02 DEN-SMT/DK...
‘Temp. min. ’ will be overruled. Time The heating system switches ON again when the outdoor Heating ON Heating OFF Heating ON temperature and the accumulated (filtered) outdoor temperature become lower than the set limit. Danfoss District Energy DEN-SMT/DK VI.GU.U1.02...
1 and are valid for other heating circuits in the controller as well, if applicable. The cut-out temperatures as well as the filter constant are to be set individually per heating circuit. Danfoss District Energy VI.GU.U1.02 DEN-SMT/DK...
“Heat cut-out” menu enabling a selection of a filter constant different from the factory setting. These different values have to be set in both the “Summer” and “Winter” menu. Danfoss District Energy DEN-SMT/DK VI.GU.U1.02...