Operating Guide ECL Comfort 310, application A377
MENU > Settings > Application
P demand
The circulation pump in the master circuit can be controlled in relation to
the master circuit's demand or slave circuit's demand.
See Appendix "Parameter ID overview"
Heating applications:
OFF:
The circulation pump is ON when the desired flow
temperature in the heating circuit is higher than the
value set in 'P heat T' .
ON:
The circulation pump is ON when the desired flow
temperature from slaves is higher than the value set in
'P heat T' .
Cooling applications:
OFF:
The circulation pump is ON when the desired flow
temperature in the cooling circuit is lower than the value
set in 'P cool T' .
ON:
The circulation pump is ON when the desired flow
temperature from slaves is lower than the value set in
'P cool T' .
MENU > Settings > Application
DHW priority (closed valve / normal operation)
The heating circuit can be closed when the controller acts as slave and when
DHW heating / charging is active in the master.
See Appendix "Parameter ID overview"
OFF:
The flow temperature control remains unchanged
during active DHW heating / charging in the master
controller.
ON:
The valve in the heating circuit is closed* during active
DHW heating / charging in the master controller.
* The desired flow temperature is set to the value set in
'Frost pr. T'
MENU > Settings > Application
Cont. T control
The desired DHW heating / charging temperature can be lowered when the
DHW heating / charging procedure has elapsed.
See Appendix "Parameter ID overview"
OFF:
The desired heating / charging temperature is lowered
to 10 °C. Typically, the DHW is circulated through the
DHW tank.
ON:
The desired heating / charging temperature is lowered
to the desired DHW temperature. Typically, the DHW
is circulated through the heat exchanger in order to
compensate for the heat loss in the DHW circulation
pipe.
96 | © Danfoss | 2017.10
1x050
The circulation pump is always controlled according to frost protection
conditions.
1x052
This setting must be considered if this controller is a slave.
1x054
VI.GU.F6.02