Output Holding Time During System Switching In The Multiplexed Remote I/O Network For Redundant System - Mitsubishi Electric QJ71LP21 Reference Manual

Q corresponding melsecnet/h network system
Hide thumbs Also See for QJ71LP21:
Table of Contents

Advertisement

3 SPECIFICATIONS
3.3.4 Output holding time during system switching in the multiplexed remote I/O network for
redundant system
3 - 46
In the multiplexed remote I/O network for redundant system, if an error occurs in the
multiplexed remote master station of the control system, the multiplexed remote sub-
master station of the standby system takes over the control of remote I/O stations. At
the time of system switching, remote I/O stations hold the outputs (data).
The output holding time of remote I/O stations during system switching differs with the
reason of system switching. In addition, it is affected by the CPU system switching
time and the switching time between multiplexed remote master station and
multiplexed remote sub-master station.
The following shows the calculation formula of output holding time for each reason for
system switching.
(1) When a power failure or CPU module stop error occurs
Multiplexed remote master station
Control system
standby system
Remote I/O station (R) Remote I/O station (R) Remote I/O station (R)
(a)
CPU system switching time < System switching time from the multiplexed
Control system
Standby system
Output holding time of remote I/O station
[Output holding time (Toh)]
Toh = Ds2 + Scan [ms]
Ds2: Switching time from the multiplexed remote master station to the
multiplexed remote sub-master station [ms]
Scan: Scanning time of the redundant CPU [ms]
Multiplexed remote sub- master station
Standby system
remote master station to the multiplexed
remote sub-master station
A power failure has occurred on the control system
Scan
standby system CPU
control system CPU
MELSEC-Q
control system
Ds2
Toh
3 - 46