APPENDIX
No.
Name
SB0007
Clear forward loop
(7)
transmission errors
SB0008
Clear reverse loop
(8)
transmission errors
6
SB0009
Clear loop switch count
(9)
SB000A
Clear transient
(10)
transmission errors
SB000B
Transient transmission
(11)
error area setting
SB0011
Data link operation
(17)
designation
Remote sub-master
SB0014
station switching
(20)
command
System switching
SB0018
monitoring time setting
(24)
valid flag
SB0020
Module status
(32)
SB0040
Network type
(64)
(host)
Host station's redundant
SB0041
function support
(65)
information
SB0042
Power supply status of
(66)
host
SB0043
Online switch
(67)
(host)
6: The SB0009 should be kept on until the SW00CE becomes "0."
App - 4
Table 1 Special link relay (SB) list (Continued)
Description
Clears the line abnormal detection (SW0CC) of the forward loop
side to 0.
Off: Clear not instructed
On: Clear instructed (valid when on)
Clears the line abnormal detection (SW0CD) of the reverse loop
side to 0.
Off: Clear not instructed
On: Clear instructed (valid when on)
Clears the loop switch count (SW0CE to 0E7) to 0.
Off: Clear not instructed
On: Clear instructed (valid when on)
Clears the transient transmission errors (SW0EE, SW0EF) to 0.
Off: Clear not instructed
On: Clear instructed (valid when on)
Designates whether to overwrite or retain the transient
transmission errors (SW0F0 to SW0FF).
Off: Overwrite
On: Retain
Designates the data link operation.
Off: No switch instruction
On: Switch instruction (valid when on)
When On is detected, data link switches from Online (normal
data link) operation to Online (debug) operation, or from Online
(debug) operation to Online (normal operation).
SB0011
Debug operation
Forcibly directs the remote sub-master station that is performing
master operation to shift to sub-master operation. (It is invalid for
the redundant system.)
Off: Without directive
On: With directive
Indicates whether the system switching monitoring time setting
(SW0018) is valid or invalid in case of a data link error.
Off: Invalid
On: Valid (valid at the time of startup)
Indicates the network module status.
Off: Normal
On: Abnormal
Indicates the network type set with the parameters of the host's
network module.
Off: PLC to PLC network
On: Remote I/O network
Indicates the station supports the redundant function or not.
Off: Redundant function not supported
On: Redundant function supported
Indicates the external power supply status to QJ71LP21S-25.
(When using QJ71LP21-25, 0 is ON.)
Off: Not supplied
On: Supplied
Indicates the mode set by the switch of the host's network
module.
Off: Online (mode setting is 0 or 4); "Parameter setting mode
becomes valid"
On: Other than online (mode setting is other than 0)
2
Online operation
Debug operation
MELSEC-Q
Use permitted/prohibited
Remote
Control
Normal
master
station
station
station
Optical Coaxial Optical Coaxial Optical Coaxial Optical Coaxial
Remote I/O
station
App - 4