8 TROUBLESHOOTING
Error No.
Description of error
F70C
System error
F70E
System error
F710
System error
F711
System error
F712
System error
F781
System error
F782
Connection target specification error
F783
System error
F7C1
Host station channel in use
F7C2
Target station channel in use
F7C3
Arrival monitoring timeout
F7C4
Resend count-out
F7C5
SEND instruction target station error
F7C6
Channel number setting out of range
Target station specification error
F7C7
(host station specification)
F7C8
Execution type specification error
F7C9
Resend count setting out of range
F7CA
Arrival monitoring time setting out of range
Sent data length setting out of range
F7CB
(SEND instruction)
8 - 28
Table 8.1 Error code list (Continued)
The cable is faulty, or the hardware of the network module is faulty.
If a communication error has occurred, review the cable.
If not, the hardware of the network module is faulty.
Contact your local Mitsubishi representative.
The hardware of the network module is faulty.
Contact your local Mitsubishi representative.
The hardware of the CPU or network module is faulty.
Contact your local Mitsubishi representative.
Check if C24 connection or CC-Link connection is specified for access to other
stations.
If the setting is correct, the hardware of the CPU or network module is faulty.
Contact your local Mitsubishi representative.
The hardware of the network module is faulty.
Contact your local Mitsubishi representative.
The same channel cannot be used at the same time.
Change the channel number.
Alternatively, do not use the same channel at the same time.
Retry the SEND instruction after a little while.
Check if the target station uses the channel concerned to execute the
instruction, or if RECV processing is executed.
Check if another station executes the SEND instruction to the target station's
channel.
<When this error occurs by the RECV instruction>
When another station is executing the SEND instruction, increase the value of
the arrival monitoring time.
Alternatively, start the RECV instruction by turning the RECV instruction
execution request flag to ON.
<When this error occurs in other cases>
Increase the value of the arrival monitoring time.
Confirm the operation status of the target station, the network status, and the
relay station status (in the case of sending to other network).
Increase the arrival monitoring time.
Re-execute the REMFR/REMTO instruction.
Confirm the operation status of the target station, the network status, and the
relay station status (in the case of sending to other network).
Review the target network number and target station No. in the request control
data of send/receive instructions.
Set the channel numbers of the host station and of the target station in the
request control data of send/receive instructions within a range between 1 and
64.
Specify the target station number in the request control data of send/receive
instructions to other than the number of host station.
When the execution/abnormal completion type in the request control data of
send/receive instructions is specified for all stations or groups, set "No arrival
confirmation" for the execution type.
Set the resent count of the request control data of send/receive instructions
within a range between 0 and 15 (times).
Set the arrival monitoring time of the request control data of send/receive
instructions within a range between 0 and 32767 (seconds).
Set the sent data length of the request control data of the SEND instruction
within a range between 1 and 960 (words).
Corrective measure
MELSEC-Q