Mitsubishi Electric QJ71LP21 Reference Manual page 151

Q corresponding melsecnet/h network system
Hide thumbs Also See for QJ71LP21:
Table of Contents

Advertisement

6 PROGRAMMING
(Station No. 2 baton pass status)
Write command
REMTO instruction completion device signal
6 - 4
If the initial settings for the buffer memory of the intelligent function module on a
remote I/O station are set by a dedicated link command (REMTO instruction), write the
program so that when only that remote I/O module is reset (by turning the remote I/O
module power supply off or by using the remote I/O module reset switch), the remote
master station will detect that condition and will once again execute the initial settings
in the intelligent function module.
This program is for resetting the intelligent function module on the remote I/O station
whenever the remote I/O station is reset.
CPU module
Master module
1)
REMTO
Initial setting: 10
CPU module
Master module
2)
3) 1) is executed once again.
POINT
When the intelligent function module parameters (initial settings) are written to the
remote I/O station, the intelligent function module initial settings are automatically
set, even if the remote I/O station is reset.
The following cases may occur when performing the initial settings to the intelligent
function module.
(a)
Analog-digital conversion module Q64AD A/D conversion permit/prohibit
setting.
(b)
Digital-analog conversion module Q62DA D/A conversion permit/prohibit.
The operating status of the remote I/O station can be confirmed by the special register
for the links for each station baton pass status (SW70 to SW73).
Remote I/O
Intelligent function
module
module
Buffer memory
10
Remote I/O
Intelligent function
module
module
Buffer memory
10
0
Reset
Initial setting program
(REMOTE instruction)
MELSEC-Q
6 - 4