8 TROUBLESHOOTING
Error Code
Error Messages
*1
(SD0)
1415
CONTROL-BUS.
ERR.
1416
1417
SYS. UNIT DOWN
1421
*3
1500
AC/DC DOWN
DUAL DC DOWN
*4
5V
1510
SINGLE PS. DOWN
*5
DC DOWN 5V
1520
SINGLE PS.
ERROR
*3
1530
DC DOWN 24V
1600
BATTERY
*16
1601
ERROR
1602
*1
: Characters in parentheses ( ) indicate the special register numbers where individual information is being stored.
*3
: This can only be detected in redundant systems. Detection is possible in either the control system or the standby system.
*4
: This can only be detected in the redundant system control system.
*5
: This can be detected in either a standalone system or a redundant system. However, in a redundant system it can only be detected in the control system.
*16 : When BATTERY ERROR occurs, the BAT. ALM LED turns on.
8 - 45
Table8.2 Error code
Common Information
Individual Information
(SD5 to 15)
(SD16 to 26)
Base No.
Unit No.
----
----
----
----
Base No./
Power supply No.
----
Base No./
Power supply No.
----
Drive Name
LED Status
RUN
ERROR
----
Off
Flicker
----
Off
Flicker
----
Off
Flicker
----
Off
Flicker
----
On
Off
----
On
On
----
On
On
----
Off
Flicker
----
On
On
----
On
On
Off
----
On
On
MELSEC-Q
Operating
Statuses of
Diagnostic Timing
CPU
When an END
Stop
instruction executed.
At power ON/At
Stop
reset
Stop
Always
Stop
Always
Continue
Always
Continue
Always
Continue
Always
Stop
Always
Continue
Always
Continue
Always
Continue
Always
8 - 45