Multiple Remote I/O Network (Qnphcpu Only); Configuration - Mitsubishi Electric QJ71LP21 Reference Manual

Q corresponding melsecnet/h network system
Hide thumbs Also See for QJ71LP21:
Table of Contents

Advertisement

2 SYSTEM CONFIGURATION

2.2 Multiple Remote I/O Network (QnPHCPU Only)

2.2.1 Configuration

2 - 4
A multiplexed remote I/O network system includes a multiplexed remote master station
and a multiplexed remote sub-master station. The multiplexed remote sub-master
station takes control of remote I/O stations when the multiplexed remote master station
fails.
Always assign station No. 0 to the multiplexed remote master station.
It is allowed to assign any of station number 1 to 64 to the multiplexed remote sub-
master station, provided that the number does not overlap with that of remote I/O
station.
63 remote I/O stations can be connected in an optical loop system, 31 stations in a
coaxial bus system.
POINT
Only the QnPHCPU is the CPU module that works as a multiplexed remote master
station and multiplexed remote sub-master station.
The Q02CPU, Q02HCPU, Q06HCPU, Q12HCPU and Q25HCPU do not work as a
multiplexed remote master station and multiplexed remote sub-master station.
Station No. 0
(Multiplexed remote
master station)
QnPH
QJ71
CPU
LP21
QJ72
I/O
I/O
LP25
Station No. 64
(Remote I/O station)
Up to 63 remote I/O stations can be connected in an optical loop system.
Up to 31 stations can be connected in a coaxial bus system.
Station No. 1
(Multiplexed remote
sub-master station)
QnPH
QJ71
CPU
LP21
Optical fiber cable
QJ72
I/O
I/O
LP25
Station No. 4
(Remote I/O station)
MELSEC-Q
Station No. 2
(Remote I/O station)
QJ72
I/O
I/O
LP25
QJ72
I/O
I/O
LP25
Station No. 3
(Remote I/O station)
2 - 4

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents