6.15 2nd acceleration/deceleration
6.15.1 Switching acceleration/deceleration time 1 & 2
:Acceleration time 2
:Deceleration time 2
: Acceleration/deceleration 1 & 2 switching frequency
Function
Acceleration and deceleration times can be set individually. Select from the following two methods for
selecting and switching.
[Parameter setting]
Title
Acceleration time 2
6
Deceleration time 2
1) Switching according to frequency (automatically switching from the set frequency
to the acceleration/deceleration time)
[Parameter setting]
Title
Output frequency [Hz]
1) Switching by frequency
2) Switching by terminal
Function
Function
Acceleration/deceleration 1 & 2
switching frequency
Set frequency
0
(1)
(1) Acceleration at ramp of
acceleration time
(2) Acceleration at ramp of
acceleration time
Adjustment range
0.0 - 3000 (s)
0.0 - 3000 (s)
Adjustment range
0.0 (disabled),
0.1-
(2)
(3)
(3) Acceleration at ramp of
acceleration time
(4) Acceleration at ramp of
acceleration time
F-40
E6581595
Default setting
10.0
10.0
Default setting
0.0
Time [s]
(4)