[Alarm information]
Each message in the table is displayed to give a warning but does not cause the inverter to trip.
Error code
Name
Auto-tuning
External power supply
input
logic switching check
alarm
Source logic switching
check alarm
Sink logic switching check
alarm
Password verification
/
result
Switching display of
/
Easy setting mode /
Standard setting mode
Input requirement of region
setting
Note 2)
No trip of past trip
No detailed information of
past trip
Note 2) is blinking when setup menu starts. Key operation is not allowed.
But parameter set doesn't blink as same as other parameters.
[Pre-alarm information]
Each message in the table is displayed to give a warning but does not cause the inverter to trip.
The following error code and the frequency will flash alternately.
Error code
Name
Overcurrent pre-alarm
Overvoltage pre-alarm
Overload pre-alarm
Overheat pre-alarm
Communication pre-alarm
If two or more problems arise simultaneously, one of the following pre-alarms appears and blinks.
, ,
The blinking alarms , , , h, t are displayed in this order from left to right.
Description
Auto-tuning in process
The input terminal was switched to sink
logic of external power supply input
(+24V).
The input terminal was switched to
source logic.
The input terminal was switched to sink
logic.
After the password setting (f738), the
password was input to f739 (password
verification).
The EASY key was pushed in the
standard monitor mode.
Power was supplied to the inverter at first
time
Set the parameter set to 0.
Set the parameter typ to 13.
No new record of past trip, after past trips
were clear.
The detailed information of past trip is
read by pushing the center of setting dial
during blinking nerr ⇔ number.
Description
When a current flows at or higher than the over current stall
prevention level.
When a voltage is generated at or higher than the over voltage
stall prevention level.
When a voltage is generated at or higher than the over voltage
stall prevention level.
Even if it was lower than the over voltage stall prevention level,
when a voltage is generated at sharp increse.
When the cumulative amount of overload reaches 50% or
more of the overload trip value.
When the main circuit element temperature reaches the
overload pre-alarm level.
When the overheat protection pre-alarm level is reached.
When the communication was broken off at or higher than the
over parameter f803 setting.
M-5
Remedies
Normal if it the message disappears after a few
seconds.
After removing connection of the control circuit
terminals reset or turn the power off and then back
on again. This switches the logic.
If the password is correct, pass is displayed and
if it is incorrect, fail is displayed.
When easy is displayed, setting mode becomes
easy setting mode. When std is displayed, it
becomes standard setting mode.
Set a region setting by using setting dial.
Refer to section 3.1.
Normal operation.
Normal operation.
To be returned by pressing MODE key.
Remedies
Same as (overcurrent)
Same as (overvoltage)
Same as (overload)
Same as (overheat)
Same as err5 (communication
fault)