[Parameter setting]
Title
Detection of output short-circuit at

start-up
6.16.9 Over-torque trip
 : Over-torque trip/alarm selection
 : Over-torque detection level
 : Over-torque detection time
 : Over-torque detection hysteresis
 Function
If the torque value exceeds the value set at  and doesn't return below -
for a time that exceeds the value set at , tripping or output alarm will be activated.
 is displayed in the event of a trip.
=: .......... No tripping (FL relay deactivated).
An over-torque alarm can be put out by setting the output terminal function selection
parameter.
=: .......... The inverter is tripped (FL relay activated) only after a torque exceeding the -
specified level has been detected for more than the -specified time.
[Parameter setting]
Title
Over-torque trip/alarm selection

Over-torque detection level

Over-torque detection time

Over-torque detection hysteresis

Note: = 0.0 seconds is the shortest time detected on control.
Function
0: Each time (standard pulse)
1: Only one time after power on
(standard pulse)
2: Each time (short pulse)
3: Only one time after power on
(short pulse)
Function
0: Alarm only
1: Tripping
0 (disabled),
1-200(%)
0.0-10.0 (s)
0-100 (%)
F-49
Adjustment range
Default setting
Adjustment range
Default setting
Note
E6581595
0
6
0
150
0.5
10