6.18.2 Changing the unit (A/V) from a percentage of current
and voltage
 :Current/voltage unit selection
 Function
These parameters are used to change the unit of monitor display.
%  A (ampere)/V (volt)
Current 100% = Rated current of inverter
100 V class: Input voltage 100% = 100Vac
Output voltage 100% = 200Vac
200 V class: Input/output voltage 100% = 200Vac
 Example of setting
During the operation of the VFNC3-2037P (rated current: 16.7A) at the rated load (100% load), units are
displayed as follows:
1) Display in percentage terms
%
Output current:
 
%
 
Input voltage:
[Parameter setting]
Title
Function
Current/voltage unit

selection
*
The  converts the following parameter settings:
 A display Current monitor display: Load current, torque current
Motor electronic-thermal protection level 1 & 2
DC braking current
Stall prevention level 1 & 2
Small current detection current
 V display: Input voltage, output voltage
Note) Base frequency voltage 1 & 2(, ) always displayed in the unit of V.
2) Display in amperes/volts
.
100%

100%
Adjustment range
0: %
1: A (ampere) / V (volt)
F-57
Output current:
16.7A
Input voltage:
200V
, 

, 

E6581595
6
Default setting
0