Toshiba TOSVERT VF-nC3 Instruction Manual page 140

Hide thumbs Also See for TOSVERT VF-nC3:
Table of Contents

Advertisement

1) Example of External connection
②Feedback value: Current signal input (4-20mA)
Feedback signals (1)DC : 4~20mA (2)DC : 0~10V (3)DC : 0~5V
2) Selecting PID set value and feedback value
PID set value (frequency) and feedback value can be combined as follows for the PID control.
①PID set value
Frequency setup mode selection:  Note 1
1: Setting dial 1 (press in center to save)
2: Setting dial 2 (save even if power is off)
3: RS485 communication
5: UP/DOWN from external logic input
Preset-speed operation (,  are all possible)
Note 1: Do not set  (Terminal VI).
Note 2: Do not set  (Logic input).
3) Setting PID control
Set : PID control=1(Enabled)
(1) Set : Acceleration time and : Deceleration time to the system fitting values.
(2) To limit the output frequency, set parameters : Upper limit frequency and : Lower limit frequency.
If PID set value are set with the setting dial, however, the process quantity setting range will be limited by
the settings of  and .
Note 3: Assigning the terminal function number 36 (PID control prohibition) to an input terminal. PID control
function is stopped temporarily while the terminal is ON.
Inverter
R/L1
U/T1
S/L2
V/T2
T/L3
W/T3
(1) Panel setting
①PID set value setting
(1) Panel keypad setting
VI
(2) Internal preset-speed
Setting dial
setting
CC
F-33
Motor
M
Pressure
Pressure
transmitter
transmitter
P
Pump
②Feedback value
Analog/logic input Selection
(VI terminal): f109
Note 2
0: Voltage signal input (0-10V)
1: Current signal input (4-20mA)
3: Voltage signal input (0-5V)