5.5

Selection of operation mode

 : Command mode selection
 : Frequency setting mode selection
 Function
These parameters are used to specify which input device (panel keypad, terminal block, or RS485
communication) takes priority in entering an operation stop command or frequency setting mode (terminal
VI, setting dial, RS485 communication, or UP/DOWN from external logic).
<Command mode selection>
[Parameter setting]
Title

5
Programmed value
Terminal board
:
operation
Panel keypad
:
operation
RS485
:
communication
* There are two types of function: the function that conforms to commands selected by , and the function
that conforms only to commands from the terminal board. (function number 108, 109) See the table of input
terminal function selection in section 11.6.
* When priority is given to commands from a linked computer or terminal board, they have priority over the setting
of .
<Frequency setting mode selection>
[Parameter setting]
Title

● When frequency setting by an extension panel option, fmod is set to 1 or 2.
Function
Command mode selection
ON and OFF of an external signal run and stop operation.
Press the
Operation can also be done from the extension panel.
Run/stop operations by RS485 communication from an external device.
 Refer to section 6.19.
Function
Frequency setting mode selection
Adjustment range
0: Terminal board
1: Panel keypad (including extension panel)
2: RS485 communications
RUN
STOP
and
keys on the panel keypad to run and stop.
Adjustment range
0: Terminal board VI
1: Setting dial 1 (press in center to save)
2: Setting dial 2 (saved even if power is off)
3: RS485 communication
4: -
5: UP/DOWN from external logic input
E-10
E6581595
Default setting
1
Default setting
2

Hide quick links:

Advertisement

Table of Contents