7.3.2
You can set the frequency settings by inputting an analog current signal of 4 (0) to 20mA dc between the VI and
CC terminals.
The following shows examples when the run command is input from the terminal.
Title
* Depends upon the setup menu settings. Refer to section 11.5.
7
Power
Supply
* Connect a single-phase
input model to R/L1 and
S/L2/N.
Settings depending on current (4 to 20 mA) input
Function
Command mode selection
Frequency setting mode
selection
Analog/logic input selection
(VI terminal)
VI input point 1 setting
VI input point 1 frequency
VI input point 2 setting
VI input point 2 frequency
Analog input filter
MCCB
VF-nC3
R/L1
S/L2
W/T3
T/L3
FLA
FLB
FLC
P24
OUT
NO
CC
VI
P5
= : Current signal input (4 – 20mA)
Adjustment range
0 - 2
0 - 5
0: Voltage signal input (0 - 10V)
1: Current signal input (4 - 20mA)
2: Logic input
3: Voltage signal input (0 – 5V)
0 - 100%
0.0 - 400.0Hz
0 - 100%
0.0 - 400.0Hz
4 - 1000 ms
Run and stop settings
Motor
U/T1
IM
V/T2
Setting characteristics for the frequency
S1
S2
Connecting and calibrating the frequency
Forward
run
F
Reverse
R
run
FM
CC
+
4 (0) to 20 mA dc
-
G-12
Default setting
Setting example
1
(panel keypad)
(terminal board)
2
(setting dial)
(terminal board VI)
0
(Current signal
(4 – 20mA))
0
0.0
100
*
64
You can switch between forward run (F) and
reverser run (R), and run/stop with external
signals.
setting signal and operation frequency
Set characteristics at two points in the
diagram below.
meter
Select the type of meter connected at
and calibrate.
Refer to section 3.4 for details.
Hz
Point 1
0%
20%
100%
(0 to 4
to
20 mA)
Frequency setting signal
E6581595
0
0
1
20(0)
0.0
100
60.0
64
Point 2
%
Current input