Motor Control File (File B) - Allen-Bradley PowerFlex 70 User Manual

Adjustable frequency
Hide thumbs Also See for PowerFlex 70:
Table of Contents

Advertisement

No. Parameter Name and Description
026 [Rated kW]
32
Drive power rating.
027 [Rated Volts]
The drive input voltage class (208, 240,
400 etc.).
028 [Rated Amps]
The drive rated output current.
029 [Control SW Ver]
Main Control Board software version.

Motor Control File (File B)

No. Parameter Name and Description
040 [Motor Type]
Set to match the type of motor connected.
041 [Motor NP Volts]
Set to the motor nameplate rated volts.
042 [Motor NP FLA]
Set to the motor nameplate rated full load
amps.
043 [Motor NP Hertz]
Set to the motor nameplate rated
frequency.
044 [Motor NP RPM]
Set to the motor nameplate rated RPM.
045 [Motor NP Power]
Set to the motor nameplate rated power.
32
046 [Mtr NP Pwr Units]
The power units shown on the motor
nameplate.
Programming and Parameters
Values
Default:
Read Only
Min/Max:
0.37/15.0 kW
Display:
0.1 kW
Default:
Read Only
Min/Max:
Based on Drive Rating
Display:
0.1 VAC
Default:
Read Only
Min/Max:
1.1/32.2 Amps
Display:
0.1 Amps
Default:
Read Only
Min/Max:
0.000/65.256
Display:
0.001
Values
Default:
0
"Induction"
Options:
0
"Induction"
1
"Synchr Reluc"
2
"Synchr PM"
Default:
Based on Drive Rating
Min/Max:
0.0/[Rated Volts]
Display:
0.1 VAC
Default:
Based on Drive Rating
0.0/[Rated Amps] × 2
Min/Max:
Display:
0.1 Amps
Default:
Based on Drive Cat. No.
Min/Max:
5.0/400.0 Hz
Display:
0.1 Hz
Default:
1750 RPM
Min/Max:
60/24000 RPM
Display:
1 RPM
Default:
Based on Drive Rating
Min/Max:
0.0/100.0
Display:
See
[Mtr NP Pwr Units]
Default:
Based on Drive
Rating
Options:
0
"Horsepower"
1
"kiloWatts"
3-9
196
047
048
046