Allen-Bradley PowerFlex 70 User Manual page 72

Adjustable frequency
Hide thumbs Also See for PowerFlex 70:
Table of Contents

Advertisement

3-36
Programming and Parameters
No. Parameter Name and Description
380
[Digital Out1 Sel]
[Digital Out2 Sel]
384
Selects the drive status that will energize
a (CRx) output relay.
(1)
Contacts shown on page
drive powered state with condition not
present. For functions such as "Fault"
and "Alarm" the normal relay state is
energized and N.O. / N.C. contact
wiring may have to be reversed.
381
[Dig Out1 Level]
[Dig Out2 Level]
385
Sets the relay activation level for options
10 – 15 in [Digital Outx Sel]. Units are
assumed to match the above selection
(i.e. "At Freq" = Hz, "At Torque" = Amps).
382
[Dig Out1 OnTime]
[Dig Out2 OnTime]
386
Sets the "ON Delay" time for the digital
outputs. This is the time between the
occurrence of a condition and activation
of the relay.
383
[Dig Out1 OffTime]
[Dig Out2 OffTime]
387
Sets the "OFF Delay" time for the digital
outputs. This is the time between the
disappearance of a condition and
de-activation of the relay.
Values
Default:
Options:
1-14
are in
Default:
Min/Max:
Display:
Default:
Min/Max:
Display:
Default:
Min/Max:
Display:
1
"Fault"
4
"Run"
(1)
1
"Fault"
(1)
2
"Alarm"
3
"Ready"
4
"Run"
5
"Forward Run"
6
"Reverse Run"
7
"Auto Restart"
8
"Powerup Run"
9
"At Speed"
10
"At Freq"
11
"At Current"
12
"At Torque"
13
"At Temp"
14
"At Bus Volts"
15
"At PI Error"
16
"DC Braking"
17
"Curr Limit"
18
"Economize"
19
"Motor Overld"
20
"Power Loss"
21
"Input 1 Link"
22
"Input 2 Link"
23
"Input 3 Link"
24
"Input 4 Link"
25
"Input 5 Link"
26
"Input 6 Link"
0.0
0.0
0.0/819.2
0.1
0.0 Secs
0.0 Secs
0.0/600.0 Secs
0.1 Secs
0.0 Secs
0.0 Secs
0.0/600.0 Secs
0.1 Secs
381
385
382
386
383
002
001
003
004
218
012
137
157
147
053
048
184
380
380
380