3-28
Programming and Parameters
No. Parameter Name and Description
243
[Fault 1 Code]
245
[Fault 2 Code]
247
[Fault 3 Code]
249
[Fault 4 Code]
A code that represents a drive fault. The
codes will appear in these parameters in
the order they occur ([Fault 1 Code] = the
most recent fault).
244
[Fault 1 Time]
[Fault 2 Time]
246
[Fault 3 Time]
248
[Fault 4 Time]
250
The time between initial drive power up
32
and the occurrence of the associated
fault. Can be compared to [Power Up
Marker] for the time from the most recent
power up.
[Fault x Time] – [Power Up Marker] = Time
difference to the most recent power up. A
negative value indicates fault occurred
before most recent power up. A positive
value indicates fault occurred after most
recent power up.
259 [Alarm Config 1]
Enables/disables alarm conditions that will initiate an active drive alarm.
x
x
x
x
x
x
15
14
13
12
11
10
Nibble 4
Nibble 3
Bit #
Factory Default Bit Values
Values
Default:
Min/Max:
Display:
Default:
Min/Max:
Display:
1
1
1
x
1
1
1
1
9
8
7
6
5
4
3
2
Nibble 2
Nibble 1
Read Only
0000/9999
0000
Read Only
0.0000/429,496.7295 Hr
0.0001 Hrs
1
1
1 =Enabled
0 =Disabled
1
0
x =Reserved
242